DirectPerf 25%

DirectPerf 25%

Improve efficiency and capacity

Tate’s DirectPerf Panel uses patent pending technology to angle air towards equipment, achieving an impressive 93% Capture Index. This means 93% of the airflow delivered through the airflow panel is entering the face of the server rack, providing more capacity and energy efficiency than any other perforated airflow panel on the market with a 25% open area. Standard perf panels only achieve 30%-50% Capture Index, allowing the Directional Perf to double a traditional perf’s cooling capacity using the same amount of air. 

DirectPerf 25% Main View
Previous
Next

Key Performance Characteristics

  • 25% open area delivers 765CFM @ .1” H2O when installed without a damper
  • Directional air flow achieves a 93% Capture Index
  • Cools up to 6kW per rack at 0.10" H2O
  • Reduces capital expenditures on cooling infrastructure by 40%
  • Over 40% annual fan energy savings
  • Easily integrates into an existing 24inch raised floor system

DirectPerf 25%

Increase Energy Efficiency and Maximize Cooling Capacity

The DirectPerf has been designed to meet the cooling requirements typically associated with high air volume grate panels while still supplying the same air volume as a standard perforated panel. With the ability to cool twice the capacity of a standard panel, directional perfs can improve a facilities overall cooling capacity allowing for the addition of IT equipment without the capital investments on infrastructure.

Eliminate Waste and Improve Data Center Financial Performance

With a 93% Capture Index, wasteful by-pass airflow is virtually eliminated. The precise delivery of air to the face of the rack reduces by-pass air allowing new facilities to in-turn reduce the number of CRAH units.

Airflow Performance Information

Directional Perf CFM & Cooling Capacity 25% Open Area

Pressure
(in. H20)

No Damper
(CFM)

kW/Rack
(93% CI)

0.02 341 2.5
0.04 486 3.6
0.05 538 4.0
0.06 584 4.3
0.08 669 4.9
0.10 743 5.5
0.12 809 6.0
0.14 870 6.4
0.16 921 6.8
0.18 981 7.2
0.20 1029 7.6

*Cooling capacities were calculated using the following formula:
(CFM x Capture Index %) / 126(CFM needed to cool 1kW @ 25ºF ΔT)= kW per rack.

Product Resources & Downloads

DirectPerf 25% Datasheet 24in

DirectPerf 25% Detail (PDF) 24in

DirectPerf 25% Detail (CAD) 24in

DirectPerf 25% Specification 24in

DirectPerf 25% Panel 24in BIM

DirectPerf 25% Panel 24in BIM

DirectPerf 25% Datasheet for Woodcore 24in

DirectPerf 25% Detail for Woodcore (PDF) 24in

DirectPerf 25% Detail for Woodcore (CAD) 24in

DirectPerf 25% Datasheet 60cm

DirectPerf 25% Detail (PDF) 60cm

DirectPerf 25% Detail (CAD) 60cm

DirectPerf 25% Specification 60cm

DirectPerf 25% Panel 60cm BIM

 

The 60cm DirectPerf 25% is currently not supported on the Woodcore System's Understructure

The DirectPerf 25% is available with the factory installed Slide Damper control

Brochures-In-Floor-Cooling

In-Floor Cooling Solutions for Data Centers

Brochures-Data-Center-Opt

Data Center Optimization Solutions

Other Airflow Panel Options

Other Data Center Solutions

More About Tate

Need to talk? We're here for you.

Our team is ready to help you select the best solutions for your project.

Contact our support team

We use cookies on our website www.kingspan.com. To find out more about the cookies we use, or to change your cookie preferences i.e. to remove your consent to our use of certain categories of cookies, please visit our Cookie Policy & Control page.

Please click “Accept and close” to accept the use of cookies on our website. If you do not click “Accept and close” but continue to use this website: you thereby consent to the use of all Kingspan's cookies and third party cookies for the purposes of improving performance, improving functionality and audience measurement, in accordance with the terms laid out in our Cookie Policy & Control page; and we will assume that you have read and understood our Cookie Policy & Control page.

The Cookie Policy & Control and Website Privacy Notice were updated on 13 August 2018.