Download
The Kingspan KoolDuct System can be used for the whole HVAC Ductwork system including circular sections, areas with an access door and plenums.
Previous
Next

Why Kingspan KoolDuct Panel?

Kingspan KoolDuct Panels have a premium performance, rigid thermoset phenolic insulation core. The panels are faced on both sides with a protective 25.4 micron foil that is reinforced with a 5 mm / 0.2’ glass scrim.

The core of KoolDuct Panels have a fibre-free and closed cell insulation core, which has been manufactured with a CFC/HCFC-free blowing agent that has zero Ozone Depletion Potential (ODP) and low Global Warming Potential (GWP).
  • Fibre-free core
  • Low aged thermal conductivity
  • UL Listed
  • Low-weight
  • CFC/HCFC-free

Product Information

Product Data
Operating Recommendations
Testing and Compliance
Management Standards
Fire and Smoke Performance
Environmental Data

Product Data

Property Value
Width 1200 mm / 3.94 ft
Length 4000 mm / 12.89 ft
Thickness 20, 22 & 30 mm / 25/32”, 7/8” & 13/16”
Thermal Conductivity at 10-23oC / 50-74oF Mean 0.021 W/m.K / 0.146 Btu.in/ft2.hr.F
Density 55-60 kg/m3
Compressive Strength 200 kPa

Operating Recommendations

Property Value
Operating Temperature Limits -26oC to 85oC / -15oF to 185oF
Mean Air Velocity (Max.) 25.4 m/s / 5000fpm
Design Pressure (Max.) Positive : 100 Pa / 4 in.w.g
Negative: 750 Pa / 3 in.w.g
Application Indoor
Size Unlimited

Testing and Compliance

Standard KoolDuct Compliance
ANSI / ASHRAE / IESNA 90.1:2004, 2007 & 2010 22 & 30 mm / 7/8” or 1 3/16”
ICC 22 & 30 mm / 7/8” or 1 3/16”
BS 5422: 2009 22 & 30 mm / 7/8” or 1 3/16”

Management Standard

Standard Management Standard
ISO 9001:2008 Quality Management
ISO 14001:2008 Environmental Management
BS OHSAS 18001:2007 Health and Safety Management
ISO 50001: 2011 Energy Management

Fire and Smoke Performance

Standard Result
UL 181 Burning: Pass
Flame Penetration: 30 Minutes
Result: UL 181 Listed
UL 723 Class A
ASTM E 84 – 13a Flame Spread Index (FSI) of 10
Smoke Developed Index of 10 Class 1/A
Euroclass Bs1d0

Environmental Data

Standard Result
Green Guide Rating A
BES 6001 Excellent

Download Product Catalogue and Datasheet

Front Cover_ KoolDuct Submittal Sheet

Kingspan KoolDuct Datasheet

Featured Case Studies

Do you need help and advice on your project?

Our teams are dedicated to helping make your process as easy as possible and ensure you get the right materials for your building.

Contact us

Contact Information

Kingspan Insulation Middle East

Kingspan Insulation operates across the Middle East, Africa and Indian Subcontinent. Contact us to find your local representative. For any inquiries send an email to info@kingspaninsulation.ae

Head Office

P.O. Box 113826, Dubai Investment Park 2

Dubai, U.A.E.

Tel: +971 4 889 1000

Fax: +971 4 883 8515

We use cookies on our website www.kingspan.com. To find out more about the cookies we use, or to change your cookie preferences i.e. to remove your consent to our use of certain categories of cookies, please visit our Cookie Policy & Control page.

Please click "Accept and close" to accept the use of cookies on our website. If you do not click "Accept and close" but continue to use this website: you thereby consent to the use of all Kingspan's cookies and third party cookies for the purposes of improving performance, improving functionality and audience measurement, in accordance with the terms laid out in our Cookie Policy & Control page; and we will assume that you have read and understood our Cookie Policy & Control page.

The Cookie Policy & Control and Website Privacy Notice were updated on 13 August 2018.