What is the Euroclass System?

  • Est Time: 10 mins
  • Rating: Artboard 1Artboard 1Artboard 1
Read our blog below and watch the video above to learn more about the Euroclass System, don't forget to test you've understood everything by taking the short quiz afterwards.
 
At some point, you will most likely have heard construction products being described as, ‘A1 / non-combustible’,  ‘A2 / of limited-combustibility’, or ‘B-F / combustible’, but how is this assessed?

The three labels relate to a product’s mandatory reaction to fire classification in the UK. This can be achieved through the National classes, using the BS 476 suite of tests. However, to CE Mark (as is legally required for most construction products), products must also be classified through the Euroclass system .

How does the Euroclass system work?

The Euroclass system was introduced to harmonise standards across the EU. It categorises products into one of seven reaction to fire classes ranging from A1 (non-combustible) down to F (the worst performing class in terms of combustibility), using a defined test or combination of tests. It also provides additional classification (typically associated with reaction to fire classes D – B)  for smoke production (from s1 (little or no smoke) to s3 (substantial smoke)) and flaming droplets/particles (from d0 (none) to d2 (quite a lot)).  

During its development, the European Commission’s Fire Regulators Group wanted the system to directly address the hazards in an actual fire scenario — a fire in a room. To do this, they used a room corner test (ISO 9705-1: 2016 - Room corner test for wall and ceiling lining products) as the reference point. Crucially, this test method was specifically designed to measure the burning behaviour of internal wall and ceiling lining products.

This decision has led to flaws within the Euroclass system, particularly around the Single Burning Item (SBI) test which can be used to assess the reaction to fire of products from class A1-D.

What tests are used within the Euroclass system?

When assessing construction products (other than flooring), the Euroclass system uses four tests:

EN ISO 1182:2010 - Non-combustibility test

This is a small-scale test designed to assess whether a product will contribute towards a fire.

A small specimen is placed within the cylindrical furnace which is maintained at 750°C. During the 30 minute test, temperature changes on the surface and at the centre of the specimen are monitored via thermocouples (sensors). The specimen is also observed for signs of sustained flaming. At the end of the test, mass loss from the specimen is calculated.

The test criteria used within the Euroclass system are:
•    ∆T – temperature rise on specimen thermocouples
•    ∆m – mass loss of specimen
•    tf  - sustained flaming time

Note that data gathered from thermocouples inside the product specimen is used for information only and does not affect the classification outcome.
EN ISO 1716:2018 - Determination of the gross heat of combustion (calorific value)

This is a small-scale test designed to calculate the maximum heat release of a specimen when burned completely.

A small test specimen is ground to a powder and ignited in a pressurised oxygen atmosphere within a
calorimetric bomb. The bomb is located within water and temperature changes in the water are monitored during the burning. The gross calorific potential is then calculated based on the temperature change, specimen mass and other correction factors.

The test criteria used within the Euroclass system is:
PCS — gross calorific potential.
EN 13823:2010+A1:2014 - Single burning item (SBI) test

This is an intermediate scale test based on the reference room corner test (ISO 9705-1: 2016 - Room corner test for wall and ceiling lining products)
 
The product specimen is mounted on the trolley rig forming a room corner. It is exposed to flames with a heat release of 30 kW for a period of 20 minutes. Heat and smoke production is measured within the ducting for the exhaust hood and flame spread is observed throughout the test.

The test criteria used within the Euroclass system are:
  • Total Heat Release (THR) — the total heat released in the evaluation period
  • Lateral Flame Spread (LFS) — a simple measure of whether flames spread to the edge of the specimen
  • Fire Growth Rate Index (FIGRA) — the speed at which heat release increases throughout the full test duration
  • Total Smoke Production (TSP) — the total smoke produced during the evaluation period
  • Smoke Growth Rate (SMOGRA) — the rate at which smoke production increases during the full 20-minute exposure period.
  • Flaming droplets/particles — any droplets/particles which continue to flame for longer than 10 seconds when they reach the ground is recorded during the first 10 minutes of the test.
EN ISO 11925-2 – Single-flame source test/ignitability test

A small-scale reaction to fire test designed to determine the ignitability of a vertical product specimen when exposed to a small flame.

Where products will be used in an application where the edge may be exposed to flame, the gas burner is mounted in two positions:
•    Surface exposure – 40 mm above the bottom edge of the specimen
•    Edge exposure – at the mid-point on the bottom of the specimen (specimen thicknesses ≤ 3 mm thick) or 1.5 mm behind the surface (> 3 mm thick)

The burner is lit with a flame height of 20 mm and the test begins as soon as this makes contact with the specimen. The flame can either be applied for:
•    15 seconds (with the specimen observed for a further 5 seconds); or
•    30 seconds (with the specimen observed for a further 30 seconds).

The flame height and filter paper are observed throughout.

The test criteria used within the Euroclass system are:
•    15 second exposure with flame height not exceeding 150 mm within 20 seconds
•    30 second exposure with flame height not exceeding 150 mm within 60 seconds
•    Does filter paper ignite

How are products classified within the Euroclass system?

Below is a summary of the primary classifications within the Euroclass system:
  Class SBI Criteria
Smoke Production s1
  • SMOGRA ≤ 30 m2/s2; and
  • TSP ≤ 50 m2 within the evaluation period
Smoke Production s2
  • SMOGRA ≤ 180 m2/s2; and
  • TSP ≤ 200 m2 within the evaluation period
Smoke Production s3 Products does not comply with either of the above
Flaming Droplets/Particles d0 No flaming particles/droplets occur within the evaluation period
Flaming Droplets/Particles d1 No flaming particles/droplets lasting longer than 10s occur within the evaluation period
Flaming Droplets/Particles d2 Product does not comply with either of the above
 
You can download the full testing standard from the British Standards Institution shop: