Maintaining floor to ceiling height in residential refurbishment

Ground floors in many UK homes are uninsulated. By retrofitting insulation in these areas, it is possible to reduce annual energy bills by as much as £65 and increase thermal comfort. When choosing insulation for these refurbishment applications, it is important to look at their thermal conductivity. Insulation materials with lower thermal conductivities are more efficient and can allow a compliant U-value to be achieved with a slimmer thickness of insulation. Currie & Brown carried out an analysis to see how this can affect floor to celing height in solid floor applications.

The research looked at Kingspan Kooltherm K103 Floorboard, which has the lowest thermal conductivity of any commonly used insulation (0.018 W/m·K), and expanded polystyrene (EPS) insulation with a thermal conductivity of 0.038 W/m·K. The insulation materials were compared in two refurbishment scenarios for an existing solid concrete floor with a sand and cement screed:
  1. The sand and cement screed was removed and replaced with insulation and either a 35 mm liquid screed or 65 mm sand and cement screed;
  2. The existing floor was excavated and replaced with a 100 mm concrete slab, insulation and the sand and cement or liquid screed
All constructions were designed to achieve a maximum U-value of 0.25 W/m².K – complying with the refurbishment requirements outlined within Approved Document L1B in England & Wales.
 
The research shows that it was considerably more cost effective to remove and replace the screed layer rather than excavating the entire slab. When adopting this approach, the Kingspan Kooltherm K103 Floorboard with liquid screed was the only construction which allowed existing headroom to be retained. This also avoids potential remedial costs relating to altering floor heights, such as raising fixtures and pipework, which were not considered within the analysis.
 

Maintaining Floor to Ceiling Height White Paper

Find out more about the impact of using low lambda insulation when refurbishing residential floors

Maintaining floor to ceiling height in residential refurbishment

Find out more about ground floor insulation

Kingspan Insulation Ltd

For queries relating to insulation boards, cavity closers or membranes.

Pembridge

Leominster

Herefordshire

HR6 9LA

General enquiries: 01544 388 601

Technical advice: 01544 387 382

We use cookies on our website www.kingspan.com. To find out more about the cookies we use, or to change your cookie preferences i.e. to remove your consent to our use of certain categories of cookies, please visit our Cookie Policy & Control page.

Please click "Accept and close" to accept the use of cookies on our website. If you do not click "Accept and close" but continue to use this website: you thereby consent to the use of all Kingspan's cookies and third party cookies for the purposes of improving performance, improving functionality and audience measurement, in accordance with the terms laid out in our Cookie Policy & Control page; and we will assume that you have read and understood our Cookie Policy & Control page.

The Cookie Policy & Control and Website Privacy Notice were updated on 13 August 2018.