AU_Datacenter_AirflowPanels_GrateAire_HeroImage

DirectPerf 32%

Same cooling capacity as a typical grate

DirectPerf 32% angles the airflow toward the server rack to significantly improve energy efficiency and reduce bypass air. DirectPerf 32% provides nearly the same cooling capacity as a standard 56% open area grate using about half the airflow. The panel is designed with a unique combination of directional and vertical perforations which provides evenly distributed air flow across the entire face of a typical IT rack.

DirectPerf 32% Main View
Previous
Next

Key Performance Characteristics

  • 32% open area delivers 529 L/s @ 25 Pa when installed without a damper.
  • Directional air flow achieves a 88% Capture Index.
  • Cools up to 8kW per rack at 25 Pa.
  • Can save over 40% in annual fan energy savings.
  • Easily integrates into an existing 60cm raised floor systems

DirectPerf 32%

Tate's DirectPerf maximises energy efficiency and the overall capacity of any new or existing data centre by nearly eliminating bypass air. The precise delivery of air to the face of the rack reduces by-pass air allowing new facilities to in-turn reduce the number of CRAH units. Retrofits can set CRAH units with fixed speed fans to standby mode or adjust variable fan drives to operate at a lower static pressure, saving energy. Likewise the 88% Capture Index eliminates the need for an aisle containment roof. The facilities overall cooling capacity will also be improved allowing for the addition of IT equipment without the capital investments on infrastructure.

Airflow Performance Information

Directional Perf L/s & Cooling Capacity 32% Open Area

Static Pressure (Pa)

L/s w/No Damper

kW/Rack (88% CI)

5 251 3.7
10 351 5.2
12.5 393 5.8
15 420 6.2
20 477 7.1
25 529 7.8
30 583 8.6
35 634 9.4
40 674 10.0
45 711 10.5
50 754 11.2

*Cooling capacities were calculated using the following formula:
(L/s x Capture Index %) / 59(L/s needed to cool 1kW @ -4ºC ΔT)= kW per rack.

Downloads

DirectPerf 32% Datasheet 60cm

DirectPerf 32% Detail 60cm (PDF)

DirectPerf 32% Detail 60cm (CAD)

DirectPerf 32% Specification 60cm

The DirectPerf 32% is available with these Control options

In-Floor Cooling Brochure

In-Floor Cooling Brochure

In-Floor Cooling Solutions for Data Centres

Data Centre Optimization Brochure

Data Centre Optimisation Solutions

Commercial & Data Centre Product Solutions Guide

Tate Product Solutions Guide

Other Airflow Panel Options

Other Data Centre Solutions

Need to talk? We're here for you.

Our team is ready to help you select the best solutions for your project.

Contact our support team

More About Tate

We use cookies on our website www.kingspan.com. To find out more about the cookies we use, or to change your cookie preferences i.e. to remove your consent to our use of certain categories of cookies, please visit our Cookie Policy & Control page.

Please click "Accept and close" to accept the use of cookies on our website. If you do not click "Accept and close" but continue to use this website: you thereby consent to the use of all Kingspan's cookies and third party cookies for the purposes of improving performance, improving functionality and audience measurement, in accordance with the terms laid out in our Cookie Policy & Control page; and we will assume that you have read and understood our Cookie Policy & Control page.

The Cookie Policy & Control and Website Privacy Notice were updated on 13 August 2018.