Various products from our standard insulation, insulated panel and rainscreen facade ranges have met the requirements of BR 135 when tested to BS 8414 in specific system configurations. We publish all reports (both pass and fail). See below for more information, including specification details and downloadable classification reports. 

Read more about Kingspan and fire safety here. 


We fully recognise the concerns that are being experienced by many people as a result of the wider issue of safety of cladding systems in high-rise residential buildings. Building occupants who have a query or concern about the use of Kingspan Insulation products should contact their building owner / freeholder and request they fill out the form here and we will respond as soon as possible.

 

Insulation

Product update – Kingspan Kooltherm K15 Rainscreen Board

As part of a development project, Kingspan Insulation has made adjustments to the foil facer material of Kingspan Kooltherm K15. This change affects all Kooltherm K15 manufactured from the 18th October 2021 onwards. Please note that as a result, a number of BS 8414 system tests now have a corresponding assessment in lieu of test, in accordance with the guidance given in BS 9414: 2019. This assessment takes into consideration the change of facing material.
 

 
K15 pigeon grey 140mm insulation v2

Kingspan Kooltherm K15 Rainscreen Board with Taylor Maxwell Tampa terracotta tiles

Tested Build-up
 
  • 30mm Taylor Maxwell Tampa terracotta tiles fixed to an aluminium vertical support railing system
  • Aluminium top hat support
  • Aluminium helping hand bracket
  • AIM horizontal cavity barrier with intumescent strip
  • 140mm Kingspan Kooltherm K15 Rainscreen Board fixed to a 12mm Euroform Versapanel cement particle board
  • Two layers of 12.5mm British Gypsum Gyproc plasterboard fixed to 150mm SFS
  • Combustion chamber surround constructed from aluminium
Test Report BS 8414-2: 2005 test report - 303930 Download here
Classification Report BR 135: 2013 - 297211 Download here
Assessment Report BS 9414: 2019 – P116866-1001A Download here

For more information on the precise test build up including more detailed drawings than available within the relevant report please contact our technical department technical@kingspaninsulation.co.uk
BS8414_K15_A2CASSETTE

Kingspan Kooltherm K15 Rainscreen Board with Argeton Tampa terracotta tiles

Tested Build-up
 
  • 30mm Argeton Tampa terracotta tile fixed with Argeton Tampa clips to an Argeton aluminium vertical support railing system
  • Argeton helping hand bracket
  • AIM VRB Plus horizontal intumescent expanding cavity barrier
  • 140mm Kingspan Kooltherm K15 Rainscreen Board fixed to a 12mm Euroform Versapanel cement particle board
  • Two layers of 12.5mm British Gypsum Gyproc plasterboard fixed to 150mm SFS
  • Combustion chamber surround constructed from aluminium
Test report BS 8414-2: 2005 - P100184-1000 Download here
Classification report BR 135: 2013 - P100184-1001 Download here
Assessment Report BS 9414: 2019 – P116866-1001B Download here 

For more information on the precise test build up including more detailed drawings than available within the relevant report please contact our technical department technical@kingspaninsulation.co.uk
BS8414_K15_A2CASSETTE

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC/fr ACM Panel

Tested Build-up
 
  • Booth Muirie BML 400 rivet fixed 4mm Mitsubishi ALPOLIC/fr ACM panel (category 2 core material), with 4mm joints, to an aluminium vertical support railing system
  • Siderise RH25G 90/30 horizontal open state cavity barrier with intumescent strip
  • Siderise RSV 90/30 vertical cavity barrier
  • Aluminium helping hand bracket
  • 100mm Kingspan Kooltherm K15 Rainscreen Board fixed to 100mm blockwork substrate
  • Combustion chamber surround constructed from 5mm thick aluminium
Test report BS 8414-1: 2015+A1 2017 - P107017-1000 Download here
Classification report BR 135: 2013 - P107017-1001 Download here 
Assessment Report BS 9414: 2019 – P116866-1001C –  Download here 

For more information on the precise test build up including more detailed drawings than available within the relevant report please contact our technical department technical@kingspaninsulation.co.uk
BS8414_K15_A2CASSETTE

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC/fr ACM Panel

Tested Build-up
 
  • Booth Muirie BML 400 rivet fixed 4mm Mitsubishi ALPOLIC/fr ACM panel (category 2 core material) with 10mm joints, to an aluminium vertical support railing system
  • Siderise RH25G 90/30 horizontal open state cavity barrier with intumescent strip 
  • Siderise RSV 90/30 vertical cavity barrier
  • Aluminium helping hand bracket
  • 100mm Kingspan Kooltherm K15 Rainscreen Board fixed to 100mm blockwork substrate
  • Combustion chamber surround constructed from 5 mm thick aluminium
Test report BS 8414-1: 2015+A1 2017 - P109939-1000 Download here
Classification report BR 135: 2013 - P109939-1001 Download here
Assessment Report BS 9414: 2019 – P116866-1001E – Download here
 
For more information on the precise test build up including more detailed drawings than available within the relevant report please contact our technical department technical@kingspaninsulation.co.uk
BS8414 K15 BRICK

Kingspan Kooltherm K15 Rainscreen Board with bricks

Tested Build-up
 
  • Wienerberger Waresley Red Stock bricks
  • Siderise Lamatherm RH25G-90/30 stone wool horizontal cavity barriers with intumescent strip
  • Siderise Lamatherm EW-CB30 stone wool vertical cavity barriers
  • 50mm cavity
  • 100mm Kingspan Kooltherm K15 Rainscreen board* fixed to Kingspan nilvent breather membrane and 12mm thick Versapanel cement particle board
  • Two layers of 12.5mm plasterboard fixed to Kingframe SFS comprising galvanised, cold formed steel ‘C’ -sections with 100 x 50mm vertical studs
  • Combustion chamber surround constructed from 3 mm thick aluminium
*A small area had Kingspan Kooltherm K15 Rainscreen board in an 80mm thickness.

Test report BS 8414-2: 2015 + A1:2017 - P112065-1000 Download here
Classification report BR 135: 2013 - P112065-1001 Download here
Assessment Report BS 9414: 2019 – P116866-1001F–  Download here 

For more information on the precise test build up including more detailed drawings than available within the relevant report please contact our technical department technical@kingspaninsulation.co.uk
K15 BS 8414

Kingspan Kooltherm K15 Rainscreen Board with Eternit Equitone Natura panels

Tested Build-up 

 
  • 8 mm thick Eternit Equitone Natura panels with a bird beak profile,
  • 9 - 12 mm vertical and 5 - 7 mm horizontal gaps fixed to aluminium ‘L’ and ‘T’ shaped brackets with thermal pads.
  • Siderise RVG-090/030/100-102 vertical cavity barrier.
  • Siderise RH25G-090/30/098-102 horizontal open state cavity barrier with intumescent strip.
  • 60 mm Kingspan Kooltherm K15 fixed to masonry substrate.
  • Combustion chamber surround constructed from 5 mm thick aluminium
Test Report BS 8414-1: 2015 + A1:2017 - P114679-1000. Download here.
Classification Report BR135: 2013 - P114679-1001. Download here.
Assessment Report BS 9414: 2019 – P116866-1001G -  Download here 

For more information on the precise test build up including more detailed drawings than available within the relevant report please contact our technical department technical@kingspaninsulation.co.uk
K15 with A2 ACM 20mm joints

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC A2 ACM Panel

  • 4mm thick Alpolic A2 ACM panels (Booth Murie BML 400 rivet fixed) with 20mm joints 
  • Siderise Lamatherm RH25G-90/30 stone wool horizontal cavity barriers with intumescent strip 

  • Siderise Lamatherm RV-90/30 stone wool vertical cavity barriers 

  • Galvanised steel ‘U’-shaped channels 

  • 100mm Kingspan Kooltherm K15 Rainscreen board fixed to 12mm thick Versapanel cement particle board 

  • Two layers of 12.5mm plasterboard fixed to Kingframe SFS comprising galvanised, cold formed steel ‘C’ & ‘U’-sections with 100 x 50mm studs 

  • Combustion chamber surround constructed from 5 mm thick aluminium 

Test report BS 8414-2: 2015 + A1:2017 - P109938-1000 Dowload here
Classification report BR 135: 2013 - P109938-1001 Download here 
Assessment Report BS 9414: 2019  – P116866-1001D – Download here
 
For more information on the precise test build up including more detailed drawings than available within the relevant report please contact our technical department technical@kingspaninsulation.co.uk

Other Products

K5 BS 8414

Kingspan Kooltherm K5 External Wall Board with Alumasc render

Tested Build-up 

 
  • Masonry Substrate
  • 5mm M.R. Bedding Adhesive
  • 60mm Kingspan Kooltherm K5 External Wall Board with mechanical fixings
  • 3 mm M.R. Scrim Adhesive with Alumasc Reinforcement bedded into it
  • 8 – 10 mm M.R. S4 Base Coat
  • Alumasc Silicon Primer
  • 1.5 mm Silkolitt Silicon Render
  • Combustion chamber surround constructed from render reveal
Test Report BS 8414-1: 2015 + A1: 2017 - P112107-1000
Classification Report BR 135: 2013 - P112107-1001 297211

(Reports prepared for Alumasc Exterior Building Products Ltd, White House Works, Bold Road, Sutton, St Helens, Merseyside, WA9 4JG. Please contact them for a copy of these reports.)

For more information on the precise test build up including more detailed drawings than available within the relevant report please contact our technical department technical@kingspaninsulation.co.uk

Architectural Facade Systems

QC_Karrier_-_DD_Direct_Finish_2019

Dri-Design on QuadCore® Karrier

Tested Build-up
 
  • 32mm deep mill finished aluminium cassettes installed onto outer face of QuadCore® Karrier panel
  • 80mm thick with a cover width of 1100mm Benchmark QuadCore™ Karrier panels.
  • 12.5mm plasterboard lining on 100mm deep Kingspan Kingframe SFS
  • Tenmat FF102/50 intumescent fire barrier 
  • Fashings for panels, Tata Steel XL Forte Merlin Grey
  • Flashings for cassette, Arcelor Spectrum Metallic Silver
  • 25mm Knauf insulation packing between cut joints
Test Report BS 8414-2: 2015 - P107922-1000 Download here
Classification Report BR 135: 2013 Annex B - P107922-1001 Download here
DD - K_Slab Fire Test BS 8414

Dri-Design with K-Roc Rainscreen Slab

Tested Build-up 
 
  • Dri-Design aluminium cassette of 2mm thickness, of PPC dark copper colour as finishing on the outer face
  • Air cavity 38mm thick, measured between insulation and Omega profiles
  • Siderise RV 90/30 (Siderise) Vertical open state cavity barrier
  • Siderise RH25G 90/30 (Siderise) Horizontal open state cavity barrier
  • Two layers of Kingpsan K-Roc Rainscreen slab insulation of 100mm thickness
  • Breather membrane TYVEK FireCurb (Dupont)
  • Sheathing board Y-wall (RCM) of 12mm thickness
  • Earthwool Omni fit slab insulation (KNAUF) of 100mm thickness fitted in between the studs
  • Steel frame system of steel 'C' sections with 100mm x 50mm studs
  • Air and vapour control layer of Airguard control membrane (DuPont)
  • Two layers of 15mm Knauf Wallboard (GYPROC Saint-Gobain)
Test Report BS 8414-2:2015+A1:2017 - EUI - 18 - FF - 000081A Download Here
Classification Report BR 135 third edition 2013 - EUI-18-000081A Download Here
QC Karrier Hook-On Cassette Full System Fire Test

Metallic Hook-on Cassette

Tested Build-up
 
  • 60mm BENCHMARK Aluminium Hook-on Cassette installed on vertical supports
  • 100mm BENCHMARK Wall liner panels
  • 100mm Steel frame
  • Single layer 12mm wall board
  • BENCHMARK Aluminium mullions KSHOM
  • Tenmat FF102/50 Horizontal Intumescant expanding Fire Barrier
  • Tenmat VFB Plus 30 x 75mm Intumescant Fire Barrier
Test Report BS 8414-2: 2005 - 297804 Download here
Classification Report BR 135: 2013 Annex B - 299571 Download here
Corium Brick Tile BRE Fire Resting Full System Fire Test

Corium Brick Tile

Tested Build-up
  • Galvanised mild steel support brackets
  • 220mm QuadCore wall liner panel
  • Powder coated top hat sections
  • Support rails
  • Intumescent fire barrier
  • Corium brick system facade
  • Parex Ltd Historic Pointing mortar KL
Test Report BS 8414-2: 2005 - P102340-1000 Download here
Classification Report BR 135: 2013 Annex B - P102340-1002 Download here
 
Fire Safety Evolution Panelised Facade Full System Fire Test 2019

Evolution

Tested Build-up
 
  • BENCHMARK Evolution Panel with 0.595mm outer skin and 0.32mm inner skin constructed from double sided corrosion coated S220 grade steel, filled with Kingspan Ltd Ecosafe PIR of 150mm thickness
  • Arcelor External flashings of 0.595mm thickness
  • SFS Intec self-drilling, self-tapping screws
  • SXC5 S16 - 5.5 x 160mm panel fixers
  • SXC5 S16 - 5.5 x 185mm panel fixers
  • SX14 S16 5.5 x 66mm panel fixers
  • SL2 S S16 5.5 x 28mm stitcher fasteners
  • Knauf Insulation Rocksilk Krimpact 200mm x 25mm thickness
  • No lining. Vertical hot rolled hollow sections

Test Report BS 8414-2:2005 - 293939 Download here
Classification Report BR135:2013 Annex B - 289585 Download here

Insulated Panel Systems

kingspan-quadcore-architectural-wall-panel-micro-rib-4-way-system-render-en-gb-ie

QuadCore® Architectural Wall Panels

Tested specification
 
  • Substrate: Lightweight steel frame
  • Insulation: 70mm Kingspan AWP QuadCore® insulation core
  • Fire breaks / Cavity barriers: No cavity barriers used

Test Report BS 8414-2:2015 + A1:2017 - P107923-1000 Download here
Classification Report BR 135: 2013 Annex B - P107923-1001 - Download here

Systems which have not met the requirements of BR 135


This section contains reports of BS 8414 tests with systems that have failed to meet the requirements of BR 135. Please refer to the list above, as some of the combinations of materials tested below have met the requirements of BR 135 in specific system configurations.
  • 100mm Kingspan Kooltherm K15 Rainscreen Board on SFS with Alpolic A2 ACM with panels 1150mm in height and 998m in width.
  • 100mm Kingspan Kooltherm K15 Rainscreen Board with Dri-Design Aluminum Cassette.
  • Vitracore G2 ACM with 180mm Rockwool Duo Slab Insulation
    • BS 8414-1:2015 + A1 :2017 test report: DLR1516 Rev.0
    • Classification Report as per BR135:2013 Annex A Tested as per BS 8414-1: 2015 + A1:2017: SR0894 Rev.0 
  • 100mm PIR Karrier Panel with Thermatile tile rainscreen
    • BS 8414-2: 2005 test report270772
  • 160mm Kingspan Kooltherm K15 Rainscreen Board with Alpolic A2 ACM Cassette Panel.
  • 100mm Kingspan Kooltherm K15 Rainscreen Board with 10mm Trespa Meteon FR Panel.
  • 80mm Kingspan Kooltherm K15 Rainscreen Board with 13mm Trespa Meteon FR Panel.
  •  140mm Kingspan Kooltherm K15 Rainscreen Board on SFS with CA Prime 7 Aluminium Cassette ​
    • BS 8414-2:2005 test summary report: P1000184-1002  (Non-UKAS Accredited)
 
For more information on the precise test build ups including more detailed drawings than available within the relevant report please contact our technical department technical@kingspaninsulation.co.uk
 

Archived Tests

The following tests do not have any BS 9414 assessment and therefore can only be used to support the use of product manufactured prior to the 18th October 2021. Kingspan are willing to work with any test report sponsors who wish to progress a BS 9414 assessment to incorporate the change of facing material. For more information, please contact highrisetechnical@kingspan.com
 
Kingspan Kooltherm K15 Rainscreen Board with Booth Muirie BML 100-HP aluminium cassette panel

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC A2 ACM Panel

  • Test report BS 8414-1: 2015+A1 2017 - P109971-1000 Download here
  • Classification report BR 135: 2013 - P109971-1001 Download here

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC A2 ACM Panel

  • Test report BS 8414-1: 2015+A1 2017 - P109973-1000 Download here
  • Classification report BR 135: 2013 - P109973-1001 Download here 

Kingspan Kooltherm K15 Rainscreen Board with ALPOLIC/fr ACM Panel

Kingspan Kooltherm K15 Rainscreen Board with Stofix brick cladding system

  • Test report BS 8414-2: 2005 - 303931
  • Classification report BR 135: 2013 - P100576-1000

Kingspan Kooltherm K15 Rainscreen Board with Gebrik cladding panels

Test report BS 8414-2: 2005 - P100838-1000 Download here
Classification report BR 135: 2013 - P100838-1001 Download here


 

Archived Products

This product archive displays a list of discontinued products. These are maintained to continue serving customers for informational purposes and are no longer available for sale.​

Kingspan Kooltherm K15 Rainscreen Board (with a black foil face) with Branco Michaela Granite stone cladding panels

  • Test report BS 8414-2: 2015+A1 2017 - EUI-18-FF-000131 Download here

  • Classification report BR 135: 2013 - EUI-18-FF-000131 Download here


If you require any further information, please contact our technical department technical@kingspaninsulation.co.uk