DirectAire®

Cool the same load with half the airflow

DirectAire® uses patent pending technology to angel the air towards the equipment achieving a 93% Capture Index. This means 93% of the airflow delivered through the airflow panel is entering the face of the server rack, providing the highest cooling capacity and energy efficiency of any airflow panel on the market. DirectAire has a 68% open area and a strong durable design that provides superior load performance. DirectAire is designed for a one-to-one paring with a standard 42U rack.

DirectAire Main View
Previous
Next

Key Performance Characteristics

  • Welded steel grate design
  • 68% open area delivers 1,227 L/s at 25 Pa
  • Cools over 19kW per rack at 25 Pa
  • 11.1 kN design load performance
  • Directional airflow for 93% Capture Index
  • Manual and automatic airflow controls options

DirectAire

The elimination of bypass air saves operating expenses in existing facilities and reduces capital expenditures on cooling equipment in new facilities. DirectAire superior load performance is ideal for retrofit and new construction, easily integrating into your existing raised floor system.

Improve Data Centre Financial Performance

Directional airflow panels maximise the financial performance of any new or existing data centre. The precise delivery of air provides many financial benefits for new and existing facilities.

  • Reduces bypass airflow by over 40% allowing new facilities to reduce the number of CRAH units.
  • Retrofits can set CRAH units with fixed speed fans to standby mode or adjust variable fan drives to operate at a lower static pressure, saving up to 40% in annual fan energy.
  • 93% Capture Index eliminates the need for costly aisle containment systems
  • Improves overall cooling capacity allowing for the addition of IT equipment without capital investment on infrastructure.

Easily Cool High Density Racks

DirectAire features a 68% open area, capable of delivering 1,227 L/s at 25 Pa. Each vertical vane has an angle of deflection at the top to direct the airflow towards the server rack to achieve a 93% Capture Index rate, compared to the typical airflow panels which only deliver 30-50% directly to the rack. This improvement enables DirectAire to efficiently cool up to 25kW per rack.

Airflow Performance Information

DirectAire® L/s & Cooling Capacity

Static Pressure (Pa)

L/s w/No Damper

kW/Rack (93% CI)

5 543 8.5
10 767 12.0
12.5 870 13.6
15 947 14.8
20 1094 17.1
25 1227 19.1
30 1332 20.8
35 1429 22.3
40 1518 23.7
45 1594 24.9
50 1620 25.3

                    *Cooling capacities were calculated using the following formula:(L/s x Capture Index %) / 59(L/s needed to cool 1kW @ -4ºC ΔT)= kW per rack.

Downloads

DirectAire 60cm Datasheet

DirectAire 60cm Detail (CAD)

DirectAire 60cm Detail (PDF)

DirectAire 60cm Specification

In-Floor Cooling Solutions

Tate Product Guide

Other Airflow Panel Options

Other Data Centre Solutions

Explore More of Tate

Need to talk? We're here for you.

Our team is ready to help you select the best solutions for your project.

Contact our support team

We use cookies on our website www.kingspan.com. To find out more about the cookies we use, or to change your cookie preferences i.e. to remove your consent to our use of certain categories of cookies, please visit our Cookie Policy & Control page.

Please click "Accept and close" to accept the use of cookies on our website. If you do not click "Accept and close" but continue to use this website: you thereby consent to the use of all Kingspan's cookies and third party cookies for the purposes of improving performance, improving functionality and audience measurement, in accordance with the terms laid out in our Cookie Policy & Control page; and we will assume that you have read and understood our Cookie Policy & Control page.